Echelon MPR-50 Multi-Port Router Manual do Utilizador Página 41

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 40
Symptom Troubleshooting Solutions
When using multiple MPR-50s, network
topology errors occur.
Ensure that the internal channel of each
of the MPR-50s in the network is defined
within the network tool as a separate
channel.
The MPR-50 does not pass messages larger
than 114 bytes.
The MPR-50 can support messages up to
256 bytes. Configure the router buffers
using the application described in
Appendix A, Buffer Configuration
Utility.
MPR-50 Multi-Port Router User's Guide 33
Vista de página 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 50 51

Comentários a estes Manuais

Sem comentários